Click to enlarge image
|
Model Number |
SONDAR2000 |
The SONDAR2000 is a highly developed ultrasonic level measurement system which provides non-contacting level measurement for a wide variety of applications in liquids. The unit offers not only dual point level but also differential level monitoring. The relays and mA outputs may be used as preset (or programmed as desired) to activate alarms and/or operate remote monitoring equipment and/or process control. The SONDAR2000 has an IP65 lid covering an integral LCD display and 5 buttons used for programming purpose. The SONDAR2000 also has two independent current outputs and chooses display options among Level1, Level2, Level1-Level2,Level2-Level1 and (Level+Level2),/2 at user's need.
Features
- Explosion-proof sensor
- Five optional displays
- 2respective set point relays
- Dual point & Differential Level measurement
Technical Specification
| Physical |
|
Dimension
|
Overall 240(D)x185(H) mm Sensor 67(D)x160(H) mm (XDS800)
|
|
Mounting
|
1" PF
|
|
Weight
|
Nominal 4.0Kg
|
|
Sensor Material
|
Polypropylene
|
| Performance |
|
Accuracy
|
0.2% of measured range
|
|
Resolution
|
1mm
|
|
Measuring range
|
0.3m~ 8m
|
|
Beam Angle
|
4° at -3dB from the axis
|
|
Damping Rate
|
Adjustable 0.1m/min to 100m/min
|
|
Temperature Compensation
|
Fully compensated
|
| Environmental |
|
IR Rating
|
IP68(Sensor) IP65(Controller)
|
|
Temperature
|
-20°C~60°C(Controller) -20°C~70°C(Sensor)
|
| Outputs & Power Supply |
|
Analog Output
|
4~20mA into max 750Ω
|
|
Communication
|
RS232 or RS485 (Option)
|
|
Power Supply
|
AC220V DC20~30V(Option)
|
Dimension

Terminal Connection

|
|
|
|
| |
|
|
|